Knowledge of Building Electricity: Which specifications shall be followed in neon lamp installation?


Published on:

2017-08-16

The connection wire between the secondary wire of the neon lamp special transformer and the lamp tube shall be a high-voltage insulated wire with a rated voltage greater than 15KV. The distance between the secondary wire and the surface of buildings and structures shall not be less than 20mm.

11

The installation of neon lights shall comply with the following regulations:

A. The neon tubes are in good condition without cracks;

B. The lamp tube is fixed with a special insulating bracket, which is firm and reliable. After the lamp tube is fixed, the distance from the surface of buildings and structures shall not be less than 20mm;

C. The special transformer for neon lights adopts a double-turn type, the length of the supplied lamp tube is not greater than the allowable load length, and there are rainproof measures for outdoor installation;

D. The connection wire between the secondary wire of the neon lamp special transformer and the lamp tube shall be a high-voltage insulated wire with a rated voltage greater than 15KV. The distance between the secondary wire and the surface of buildings and structures shall not be less than 20mm.